Key features

Stakeless Testing

The Fluke 1623-2 earth ground tester is able to measure earth ground loop resistances using only clamps. With this test method, two clamps are placed around the earth ground rod and each are connected to the tester. No earth ground stakes are used at all. A known, fixed voltage is induced by one clamp and the current is measured using the second clamp. Then the tester automatically determines the resistance of the earth ground rod. This test method only works if a bonded earth ground system exists for the building or structure under test, but most are. If there is only one path to ground, like at many residential applications, the Stakeless method will not provide an acceptable value and the Fall-of-Potential test method must be used.

With Stakeless testing, the earth ground rod does not need to be disconnected - leaving the bonded earth ground system intact during test. Gone are the days of spending time placing and connecting stakes for each earth ground rod on your system - a major time saver. You can also perform earth ground tests in places you’ve not considered before: inside buildings, power pylons, or anywhere you don’t have access to soil.

The Most Complete Tester

The Fluke 1623-2 is a unique earth ground tester that can perform all four types of earth ground measurement.

  • 3- and 4-Pole Fall-of-Potential (using stakes)
  • 4-Pole Soil Resistivity Testing (using stakes)
  • Selective Testing (using 1 clamp and stakes)
  • Stakeless Testing (using 2 clamps only)

Product overview: Fluke 1623-2 GEO Earth Ground Tester Kit

The Fluke 1623-2 GEO Earth Ground Tester offers data storage and download capabilities via USB port. World class accessories will simplify and speed up testing time.

Fluke 1623-2 GEO Earth Ground Tester summary

  • 3- and 4-pole Fall-of-Potential, earth resistance loop testing
  • 4-pole Soil Resistivity testing
  • Selective earth ground rod testing using 1 clamp
  • Stakeless earth ground rod testing using 2 clamps
  • IP56 rated for outdoor use
  • Rugged carrying case
  • USB data storage and transfer

Specifications: Fluke 1623-2 GEO Earth Ground Tester Kit

General Specifications
Display: 1999 digit LCDDisplay with special symbols, digit height 25 mm, fluorescent backlight
User interfaceInstant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Robust, water and dust resistantInstrument is designed for tough environmental conditions (rubber protective cover, IP56)
MemoryInternal memory storage up to 1500 records accessible via USB port
Temperature Range
Operating temperature-10°C to 50°C (14°F to 122°F)
Storage temperature-30°C to 60°C (-22°F to 140°F)
Temperature coefficient±0.1% of reading/°C < 18°C > 28°C
Intrinsic errorRefers to the reference temperature range and is guaranteed for 1 year
Operating errorRefers to the operating temperature range and is guaranteed for 1 year
Climatic classC1 (IEC 654-1), -5°C to +45°C (23° to +115° F), 5% to 95% RH
Protective typeIP56 for case, IP40 for battery door according to EN60529
SafetyProtection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: Pollution degree 2
EMC (emission immunity)IEC61326-1: Portable
Quality systemDeveloped, designed and manufactured according to DIN ISO 9001
External voltageV ext, max = 24 V (DC, AC < 400 Hz), measurement inhibited for higher values
V ext rejection> 120 dB (162⁄3, 50, 60, 400 Hz)
Measuring timeTypical 6 seconds
Max. overload250 V rms (pertains to misuse)
Auxiliary power6 x 1.5 V Alkaline (type AA LR6)
Battery life spanTypical > 3,000 measurements
Dimensions (W x H x D)250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)
Weight1.1 kg (2.43 lb) including batteries
7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
RA 3-Pole Ground Resistance Measurement (IEC 1557-5)
Switch positionRA 3-pole
Resolution0.001 Ω to 10 Ω
Measuring range0.020 Ω to 19.99 kΩ
Accuracy±(2% rdg + 3 d)
Operating error±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring voltageVm = 48 V AC
Short-circuit current> 50 mA
Measure frequency128 Hz
Probe resistance (RS)Max 100 kΩ
Auxiliary earth electrode resistance (RH)Max 100 kΩ
Additional error from RH and RSRH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
RA 4-Pole Ground Resistance Measurement (IEC 1557-5)
Switch positionRA 4-pole
Resolution0.001 Ω to 10 Ω
Measuring range0.020 Ω to 19.99 kΩ
Accuracy±(2% rdg + 3 d)
Operating error±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring voltageVm = 48 V AC
Short-circuit current> 50 mA
Measure frequency128 Hz
Probe resistance (RS + RES)Max 100 kΩ
Auxiliary earth electrode resistance (RH)Max 100 kΩ
Additional error from RH and RSRH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Monitoring of RS and RH with error indicator.
Automatic range selection.
RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
Switch positionRA 3-pole with clamp
Resolution0.001 Ω to 10 Ω
Measuring range0.020 Ω to 19.99 kΩ
Accuracy±(7% rdg + 3 d)
Operating error±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring voltageVm = 48 V AC
Short-circuit current> 50 mA
Measure frequency128 Hz
Probe resistance (RS)Max 100 kΩ
Auxiliary earth electrode resistance (RH)Max 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp )
Switch positionRA 4-pole with clamp
Resolution0.001 Ω to 10 Ω
Measuring range0.020 Ω to 19.99 kΩ
Accuracy±(7% rdg + 3 d)
Operating error±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring voltageVm = 48 V AC
Short-circuit current> 50 mA
Measure frequency128 Hz
Probe resistance (RS)Max 100 kΩ
Auxiliary earth electrode resistance (RH)Max 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
Stakeless Ground Loop Measurement (2 Clamps )
Switch positionRA 4-pole 2 clamps
Resolution0.001 Ω to 10 Ω
Measuring range0.020 Ω to 19.99 kΩ
Accuracy±(7% rdg + 3 d)
Operating error±(10% rdg + 5 d)
Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers
Measuring voltageVm = 48 V AC
Measure frequency128 Hz
Noise current (IEXT)Max. IEXT = 10 A (AC) (RA < 20 Ω)
Max. IEXT = 2 A (AC) (RA > 20 Ω)
Automatic range selection.
The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.

Models: Fluke 1623-2 GEO Earth Ground Tester Kit

Fluke 1623-2 Kit
Fluke 1623-2 GEO Earth Ground Tester Kit
Find a distributor

Includes:

  • GEO Earth Ground Tester
  • User’s Manual
  • Batteries
  • Quick Reference Guide
  • USB Cable
  • 2 Clamps
  • C1620 Professional Carrying Case
  • 4 Earth Ground Stakes
  • 3 Cable Reels

Dear Team at Fluke, Could you please provide information on how many years of warranty are included with this device? Additionally, could you guide me on where I can find detailed information about the warranty terms?

Asked by: Abdullah
The Fluke 1623-2 GEO Earth Ground Tester Kit has a 2-year warranty. For information about warranty terms, see https://www.fluke.com/en-us/support/warranties.
Answered by: FlukeCorporation
Date published: 2023-12-11
  • y_2024, m_11, d_4, h_7CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.42
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_1
  • loc_en_US, sid_3840949190708, prod, sort_[SortEntry(order=LAST_APPROVED_ANSWER_SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_fluke
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getContent, 24.38ms
  • QUESTIONS, PRODUCT
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getReviews, 23.24ms
  • REVIEWS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
Please enable cookies to view product reviews.