Fluke 437 Series II 400 Hz Power Quality Monitor and Energy Analyzer
Key features
The Fluke 437-II series helps you locate, predict, prevent and troubleshoot Power Quality Issues – 50Hz, 60Hz and 400Hz
- 400Hz (power quality) measurement(s) for avionic power systems
- PowerWave Data Capture— Quickly identify how motor and generator startups are impacting equipment performance
- Advanced Power Quality Health—At-a-glance power quality health data in real-time so you have the data you need, when you need it
Product overview: Fluke 437 Series II 400 Hz Power Quality Monitor and Energy Analyzer
If you’re dealing with aviation systems measuring key parameters at 400Hz is a must . The Fluke 437-II provides that capability (and measures at 50 and 60Hz too). is designed for users who need to get to the solution of the power quality problem as quickly as possible so that they can minimize expensive downtime. The shipboard power measurement system analyzes according to MIL-STD 1399 to automatically give a full evaluation of voltage, current and power according to the standard. This evaluation makes measurement and analysis as easy as can be. The measurement process and display of data is optimized to get to the most important information as quickly as possible. Multiple parameters are measured simultaneously and displayed in formats that quickly describe overall power quality health while giving you the detailed information you need to make better maintenance decisions. Data can be quickly accessed as simple digital values, trend graphs that give you fast insight into changes over time, waveforms, phasor diagrams or analyzed and organized into tabular format such as the event data where the magnitude, duration and time stamping enable rapid correlation to the problems you are experiencing.
PowerWave Data Capture— Quickly identify how motor and generator startups are impacting equipment performance
With PowerWave data capture you can capture three-phase high resolution voltage and current waveforms for up to five minutes along with detailed RMS voltage and current values. By analyzing the interaction of these values over time you can correlate the effects of voltage, current and frequency during the critical startup of motors and generators. PowerWave even goes beyond the standard power quality measurements allowing you to record half cycle rms values on 8 channels, frequency and instantaneous power (Vrms1/2, Arms1/2, W, Hz and scope waveforms for voltage, amps and watts)
Advanced Power Quality Health—At-a-glance power quality health data in real-time so you have the data you need, when you need it
The Fluke 430-II utilizes an integrated Power Quality Health summary that gives you an at-a-glance view of a complete range of power quality issues in real time. With a simple graphical presentation, complete with tolerance limits, you can quickly discover which power quality problems may be present on your electrical system. If you don’t know where to start or what problems might exist the advanced Power Quality Health summary will simplify the task.
AutoTrend—Quickly See the Trend
With a unique AutoTrend feature you can get fast insight into changes over time. Every displayed reading is automatically and continuously recorded without having to set up threshold levels or having to manually start the process So you can quickly view trends in voltage, current, frequency, power, harmonics or flicker on all three phases plus neutral.
Locating, Predicting, Preventing and Troubleshooting Power Quality Issues–Up to 400Hz
Higher power frequencies mean smaller and lighter transformers and motors – a critical factor in avionic and military transport applications where weight is a primary concern. The Fluke 437 Series II Power Quality and Energy Analyzer can show you the cost of energy waste due to poor power quality and is ideal for characterizing power quality, conducting load studies and capturing hard-to-find voltage events over a user-defined period of time. Designed for capturing power quality measurements in avionic and military systems, Fluke 437 Series II is the must-have 400 Hz quality analyzer.
- 400 Hz operation according to MIL-STD 1399 for use in avionic and military applications
- Get at-a-glance power quality health data in real-time so you can make better maintenance decisions
- Measure all three phases and neutral with the included flexible current probes
- Quickly see how much money you’re losing due to energy waste in terms of real dollars
- Easily see how motor startups are affecting motor drive performance
- Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
- Fluke Connect® compatible* – view data locally on the instrument, via Fluke Connect mobile app and PowerLog 430-II desktop software
Specifications: Fluke 437 Series II 400 Hz Power Quality Monitor and Energy Analyzer
Product Specifications | ||||
Volt | Model | Measurement Range | Resolution | Accuracy |
Vrms (ac+dc) | 1 V to 1000 V phase to neutral | 0.01 V | ± 0.1% of nominal voltage**** | |
Vpk | 1 Vpk to 1400 Vpk | 1 V | 5% of nominal voltage | |
Voltage Crest Factor (CF) | 1.0 > 2.8 | 0.01 | ± 5 % | |
Vfund | 0.1 V | ± 0.1% of nominal voltage | ||
Amps (accuracy excluding clamp accuracy) | ||||
Amps (ac+dc) | i430-Flex 1x | 5 A to 6000 A | 1 A | ± 0.5% ± 5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ± 0.5% ± 5 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ± 0.5% ± 5 counts | |
1mV/A 10x | 0.5 A A to 200 A (ac only) | 0.1 A | ± 0.5% ± 5 counts | |
Apk | i430-Flex | 8400 Apk | 1 Arms | ± 5 % |
1mV/A | 5500 Apk | 1 Arms | ± 5 % | |
A Crest Factor (CF) | 1 to 10 | 0.01 | ± 5 % | |
Amps½ | i430-Flex 1x | 5 A to 6000 A | 1 A | ± 1% ± 10 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ± 1% ± 10 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ± 1% ± 10 counts | |
1mV/A 10x | 0.5 A A to 200 A (ac only) | 0.1 A | ± 1% ± 10 counts | |
Afund | i430-Flex 1x | 5 A to 6000 A | 1 A | ± 0.5% ± 5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ± 0.5% ± 5 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ± 0.5% ± 5 counts | |
1mV/A 10x | 0.5 A A to 200 A (ac only) | 0.1 A | ± 0.5% ± 5 counts | |
Hz | ||||
Fluke 437 @ 50 Hz nominal | 42.500 Hz to 57.500 Hz | 0.001 Hz | ± 0.01 Hz | |
Fluke 437 @ 60 Hz nominal | 51.000 Hz to 69.000 Hz | 0.001 Hz | ± 0.01 Hz | |
Fluke 437 @ 400 Hz nominal | 340.0 Hz to 460.0 Hz | 0.1 Hz | ± 0.1 Hz | |
Power | ||||
Watts (VA, var) | i430-Flex | max 6000 MW | 0.1 W to 1 MW | ± 1% ± 10 counts |
1 mV/A | max 2000 MW | 0.1 W to 1 MW | ± 1% ± 10 counts | |
Power Factor (Cos j/DPF) | 0 to 1 | 0.001 | ± 0.1% @ nominal load conditions | |
Energy | ||||
kWh (kVAh, kvarh) | i430-Flex 10x | Depends on clamp scaling and V nominal | ± 1% ± 10 counts | |
Energy Loss | i430-Flex 10x | Depends on clamp scaling and V nominal | ± 1% ± 10 counts Excluding line resistance accuracy | |
Harmonics | ||||
Harmonic Order (n) | DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7 | |||
Inter-Harmonic Order (n) | OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7 | |||
Volts % | f | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.1 % |
r | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.4 % | |
Absolute | 0.0 to 1000 V | 0.1 V | ± 5% * | |
THD | 0.0 % to 100 % | 0.1 % | ± 2.5 % | |
Amps % | f | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.1% |
r | 0.0 % to 100 % | 0.1 % | ± 0.1% ± n x 0.4 % | |
Absolute | 0.0 to 600 A | 0.1 A | ± 5% ± 5 counts | |
THD | 0.0 % to 100 % | 0.1 % | ± 2.5 % | |
Watts % | f or r | 0.0 % to 100 % | 0.1 % | ± n x 2% |
Absolute | Depends on clamp scaling and V nominal | — | ± 5% ± n x 2 % ± 10 counts | |
THD | 0.0 % to 100 % | 0.1 % | ± 5 % | |
Phase Angle | -360° to +0° | 1° | ± n x 1° | |
Flicker | ||||
Plt, Pst, Pst (1min) Pinst | 0.00 to 20.00 | 0.01 | ± 5 % | |
Unbalance | ||||
Volts % | 0.0 % to 20.0 % | 0.1 % | ± 0.1 % | |
Amps % | 0.0 % to 20.0 % | 0.1% | ± 1 % | |
Mains Signaling | ||||
Threshold Levels | Threshold, limits and signaling duration is programable for two signaling frequencies | — | — | |
Signaling Frequency | 60 Hz to 3000 Hz | 0.1 Hz | ||
Relative V% | 0 % to 100 % | 0.10 % | ± 0.4 % | |
Absolute V3s (3 second avg.) | 0.0 V to 1000 V | 0.1 V | ± 5 % of nominal voltage | |
General Specifications | ||||
Case | Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2 | |||
Display | Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated | |||
Memory | 16GB Wi-Fi SD card for standard models or 8GB SD card for /INTL models (SDHC compliant, FAT32 formatted), up to 32GB optionally. Screen save and multiple data memories for storing data including recordings (dependent on memory size). | |||
Real-Time Clock | Time and date stamp for Trend mode, Transient display, System Monitor and event capture | |||
Environmental | ||||
Operating Temperature | 0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery | |||
Storage Temperature | -20 °C ~ +60 °C | |||
Humidity | +10 °C ~ +30 °C: 95% RH non-condensing +30 °C ~ +40 °C: 75% RH non-condensing +40 °C ~ +50 °C: 45% RH non-condensing | |||
Maximum Operating Altitude | Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V Maximum storage altitude 12 km (40,000 ft) | |||
Electro-Magnetic-Compatibility (EMC) | EN 61326 (2005-12) for emission and immunity | |||
Interfaces | Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery | |||
Warranty | Three years (parts and labor) on main instrument, one year on accessories | |||
View full family specifications » | ||||
* | ± 5 % if ≥ 1 % of nominal voltage ± 0.05 % of nominal voltage if < 1% of nominal voltage | |||
** | 50Hz/60Hz nominal frequency according to IEC 61000-4-30 | |||
*** | 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode | |||
**** | For nominal voltage 50 V to 500 V |
Models: Fluke 437 Series II 400 Hz Power Quality Monitor and Energy Analyzer
Includes:
- BC430 Power Adapter
- International Plug Adapter Set
- BP290 (Single Capacity Li-ion Battery) 28 Wh (7 hours or more)
- TLS430 Test Lead and Alligator Clip Set
- WC100 Color Coding Clips and Regional Decals
- i430flex-TF, 24 inch (61 cm) Length, 4 Clamps
- 16GB Wi-Fi SD card
- PowerLog on CD (includes operator manuals in PDF format)
- USB Cable A-B Mini
Includes:
- BC430 Power Adapter
- International Plug Adapter Set
- BP290 (Single Capacity Li-ion battery) 28 Wh (7 hours or more)
- TLS430 Test Lead and Alligator Clip Set
- WC100 Color Coding Clips and Regional Decals
- 16GB Wi-Fi SD card
- PowerLog on CD (includes operator manuals in PDF format)
- USB Cable A-B Mini
Includes:
- Firmware upgrade package to add motor analysis capabilities to existing Fluke 434, 435 and 437 Series II Power Quality Analyzers
Manuals + resources: Fluke 437 Series II 400 Hz Power Quality Monitor and Energy Analyzer
- Fluke 434 II/435 II/437 II | Users manual
- Fluke 434 II/435 II/437 II | Users manual supplement
- Power Log | Users manual
- Power Log | Users manual supplement
- 434-II, 435-II, 437-II, and 438-II (43x-II) | Statement of memory volatility
- Fluke 434-II/435-II/437-II | Service manual
- GPS 430-II | Instruction sheet
- i430-Flexi-TF | Instruction sheet