Fluke i6000sFlex AC Current Probe
Tổng quan sản phẩm: Fluke i6000sFlex AC Current Probe
The i6000sflex is an AC current probe utilising the Rogowski principle. It can be used to measure currents up to 6000 A when used in conjunction with oscilloscopes, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.
Thông số kỹ thuật: Fluke i6000sFlex AC Current Probe
Electrical Characteristics | |
Current ranges | 60 A / 600 A / 6000 A AC rms |
Output sensitivity (AC coupled) | 50 mV /5 mV / 0.5 mV per A |
Load impedance | 100 kOhm minimum |
Accuracy (at +25°C) | ±1% of range (45 – 65 Hz) |
Linearity (10% to 100% of range) | ±0.2% of reading |
Noise | 8 mV AC rms (60 A) |
2 mV AC rms (600/6000 A) | |
Frequency range | 10 Hz to 50 kHz (-3 dB) |
Phase error | < ±1° (45 – 65 Hz) |
±10° (at 20 kHz) | |
Position sensitivity (with cable > 25 mm from the coupling) | Position sensitivity: From 1% up to 3% of range with cable, depending on distance from the center (see figure left). Measurements closer than 25 mm from the coupling are typically greater than 3% of range. |
External field (with cable > 200 mm from the head) | ±1% of range |
Power supply | 2 x AA MN 1500 LR6 alkaline |
400 Hours, low battery indicator or dedicated ext power supply | |
Temperature coefficient | ±0.08% of reading per ° C |
Working voltage (see Safety Standards section) | 600 V AC rms or DC |
General Characteristics | |
Head cable length (double insulated) | 610 mm (24 in) I6000s Flex-24 |
915 mm (36 in) I6000s Flex-36 | |
Head cable diameter | 14.3 mm |
Head bend radius | 38.1 mm |
Cable length (head to electronics) | 2 m |
Output connection | 0.5 m cable terminated with safety BNC connector |
Supplied with 4 mm safety plug adaptor | |
Operating temperature range | -20 to +90°C (head) |
-20 to +85°C (electronics) | |
Storage temperature range | -40 to +105°C (head) |
-20 to +85°C (electronics) | |
Operating humidity | 15% to 85% (non condensing) |
Weight | 180 g (head), 190 g (electronics) |
Safety Standards | |
BS EN 61010 | 1: 2001 |
BS EN 61010 | 2-032: 2002 |
BS EN 61010 | 031: 2002 |
600 V rms, Category III, Pollution degree 2 | |
EMC standards | BS EN 61326: 1998 +A1, A2, and A3 |
Use of the probe on uninsulated conductors is limited to 600 V AC rms or DC and frequencies below 1 kHz |
Model: Fluke i6000sFlex AC Current Probe
Fluke-i6000s Flex-24
Fluke I6000S Flex-24 AC Current Probe
The i6000sflex is an AC current probe utilizing the Rogowski principle. It can be used to measure currents from 6 A to 6000A when used in conjunction with oscilloscopes, recorders or data loggers.