Fluke 106 Digital Multimeter/i400E Clamp Kit
Tính năng chính
Fluke 106 Palm-sized Digital Multimeter
- Voltage, resistance, continuity, capacitance
- Input terminal for ac and dc current measurements to 10 A and current
- Data hold
Fluke i400E AC Current Clamp
- Compatible with most Fluke multimeters or mV ac measurement tools with these features:
- 400 mV ac range
- 19.05 mm banana jack inputs
- Input accuracy of 2 % or greater to take full advantage of the accuracy of the product
- Input impedance of >1 M?
- 1 mV/A ac output guarantees easy current readings on you meter
- CAT III 600 V safety rating
- Specially designed to offer maximum utility in a very compact shape
- Take accurate current readings
Tổng quan sản phẩm: Fluke 106 Digital Multimeter/i400E Clamp Kit
The Fluke 106 digital multimeter is made to fit the way you work! It is designed to fit in the palm of your hand and go with you no matter where your job takes you.
The Fluke i400E AC Current Clamp is an ideal tool to extend current measurement. It is designed to work with the new Fluke 101, 106 and 107 palm sized digital multimeters, as well as most Fluke multimeters or other voltage measurement tools that accepts 19.05 mm shrouded banana plugs and has mV ac measurement functionality.
Thông số kỹ thuật: Fluke 106 Digital Multimeter/i400E Clamp Kit
Fluke 106 Palm-sized Digital Multimeter
Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, Relative humidity at 0% to 75%. Accuracy specifications take the form of: ±([% of Reading] + [Number of Least Significant Digits])
Accuracy specifications | ||||
AC volts1 | Range | Resolution | Accuracy | |
6.000 V 60.00 V 600.0 V | 0.001 V 0.01 V 0.1 V | 1.0% + 3 | ||
DC volts | 6.000 V 60.00 V 600.0 V | 0.001 V 0.01 V 0.1 V | 0.5% + 3 | |
AC millivolts | 600.0 mV | 0.1 mV | 3.0% + 3 | |
Diode test2 | 2.000 V | 0.001 V | 10% | |
Resistance (Ohms) | 400.0 O 4.000 kO 40.00 kO 400.0 kO 4.000 MO 40.00 MO | 0.1 O 0.001 kO 0.01 kO 0.1 kO 0.001 MO 0.01 MO | 0.5% + 3 0.5% + 2 0.5% + 2 0.5% + 2 0.5% + 2 1.5% + 3 | |
Capacitance3 | 50.00 nF 500.0 nF 5.000 µF 50.00 µF 500.0 µF 1000 µF | 0.01 nF 0.1 nF 0.001 µF 0.01 µF 0.1 µF 1 µF | 2% + 5 2% + 5 5% + 5 5% + 5 5% + 5 5% + 5 | |
Frequency4 Hz (10 Hz – 100 kHz) | 50.00 Hz 500.0 Hz 5.000 kHz 50.00 kHz 100.0 kHz | 0.01 Hz 0.1 Hz 0.001 kHz 0.01 kHz 0.1 kHz | NA | |
Duty cycle4 | 1% to 99% | 0.1% | NA | |
AC current (40 Hz to 200 Hz) | 4.000 A 10.00 A | 0.001 A 0.01 A | 1.5% + 3 | |
DC Current | 4.000 A 10.00 A | 0.001 A 0.01 A | 1.5% + 3 | |
1All AC, Hz, and Duty cycle are specified from 1% to 100% of range. Inputs below 1% of range are not specified. 2Typically, open circuit test voltage is 2.0 V and short circuit current is <0.6 mA. 3Specifications do not include errors due to test lead capacitance and capacitance floor (may be up to 1.5 nF in the 50 nF range). 4All AC, Hz, and Duty cycle are specified from 1% to 100% of range. Inputs below 1% of range are not specified. | ||||
Function | Overload protection | Input impedance (Nominal) | Common mode rejection ratio | Normal mode rejection ratio |
AC volts | 600 V 1 | >10 MO <100 pF 2 | >60 dB at dc, 50 Hz or 60 Hz | - |
AC millivolts | 600 mV | >1M, <100 pF | >80 dB at 50 Hz or 60 Hz | - |
DC volts | 600 V 1 | >10 MO <100 pF | >100 dB at dc, 50 Hz or 60 Hz | >60 dB at 50 Hz or 60 Hz |
16 x 105 V Hz Max 2For mV (AC), input impedance is approximately 1 MO. | ||||
General specifications | ||||
Maximum voltage between any terminal and earth ground | 600 V | |||
Display (LCD) | 6000 counts, updates 3/sec | |||
Battery type | 2 AAA, NEDA 24A, IEC LR03 | |||
Battery life | 200 hours minimum | |||
Temperature | ||||
Operating | 0 °C to 40 °C | |||
Storage | -30 °C to 60 °C | |||
Relative humidity | ||||
Operating humidity | Non-condensing when <10°C =90% at 10 °C to 30 °C =75% at 30 °C to 40 °C | |||
Operating humidity, 40 MO range | =80% at 10 °C to 30 °C =70% at 30 °C to 40 °C | |||
Altitude | ||||
Operating | 2000 m | |||
Storage | 12,000 m | |||
Temperature coefficient | 0.1 x (specified accuracy) /°C (<18 °C or >28 °C) | |||
Fuse protection for current inputs | 11A, 1000V Fast Fuse, Fluke specified part only | |||
Size (H x W x L) | 142 x 69 x 28mm | |||
Weight | 200 g | |||
IP rating | IEC 60529: IP 40 | |||
Safety | IEC 61010-1: 600 V CAT III, Pollution Degree 2 | |||
Electromagnetic environment | IEC 61326-1: Portable | |||
Electromagnetic compatibility | Applies to use the Korea only. Class A Equipment (Industrial Broadcasting and Communication Equipment)1 | |||
1This product meets requirements for industrial (Class A) electromagnetic wave equipment and seller or user should take notice of it. This equipment is intended for use in business environments and is not to be used in homes. |
Fluke i400E AC Current Clamp
Electrical specifications | |
AC current range | 1 A to 400 A |
Output signal 1 | mV/A ac |
Accuracy | 2.0% ±5 digits (45 Hz to 65 Hz) 2.5% ±5 digits (65 Hz to 400 Hz) |
Typical bandwith | 5 Hz to 20 kHz |
Working voltage | 600 V ac rms, in compliance with IEC 61010-1 and IEC 61010-2-030 |
Load impedance | 1 A to 400 A |
Maximum non-destructive current | 600 A |
Jaw inner diameter | 30 mm |
Maximum wire size | 600 MCM |
Standard plugs | 19.04 mm dual banana plugs |
Safety specifications | |
Category rating | IEC 61010-1 and IEC 61010-2-030/IEC 61010-2-031 and IEC 61010-2-032: 600 V CAT III Pollution Degree 2 |
Electromagnetic environment | IEC 61326-1: Portable |
General specifications | |
Output cable length | 1 m |
Operating temperature | -10 °C to +50 °C |
Storage temperature | -30 ºC to +60 ºC |
Relative humidity | =90% at 10 °C to 530 °C =75% at 30 °C to 540 °C =45% at 40 °C to 50 °C |
IP rating | IEC 60529: IP30 when jaw closed |
Temperature coefficients | Add 0.1 x specified accuracy for each °C above 28°C or below 18 °C. |
Operating altitude | 2,000 meters |
Storage altitude | 12,000 meters |
Vibration requirements | MIL-PRF-28800F, Class 2 |
Drop test requirements | -10 °C, 1m, 6 sides, oak wood |
Jaw impact test requirements | Follow EN/IEC 61010-2-032:2012 |
EMI, RFI, EMC | IEC/EN 61326-1 |
Dimensions (H x W x D) | 146 x 62 x 34 mm |
Weight | 150 g |
Model: Fluke 106 Digital Multimeter/i400E Clamp Kit
Includes:
- Fluke 106 Digital Multimeter
- Fluke i400E AC Current Clamp
- Tl75 Hard Point Test Lead Set